Circulating Water Tank Level Control: 80 GHz Radar Level Transmitter Case Study for Industry

2026/10/27

أحدث أخبار الشركة عن Circulating Water Tank Level Control: 80 GHz Radar Level Transmitter Case Study for Industry
Site Conditions: Industrial Circulating Water Tank

The plant operates a circulating cooling water system with an open concrete tank of 6 m height and a working level of 4.5–5.5 m. Water temperature is 30–45 °C, the surface is agitated by the returning water from the tower, and in summer a stable foam layer forms on part of the surface. The tank supplies the cooling water pumps; a low level means pump cavitation and a lost production run, so the level signal is used both for indication and for make-up water valve control.

Field parameter Typical value Engineering consequence
Tank height / working level 6 m / 4.5–5.5 m Level control band is narrow, so repeatability matters more than absolute accuracy
Water temperature 30–45 °C Warm, humid air above the surface condenses on cold surfaces
Surface condition Agitation, foam in summer Contact devices swing and foul; foam weakens echo returns
Control use Make-up valve modulating control Signal must be stable; noisy output causes valve hunting
Existing system DCS with 4–20 mA input cards Analog output is the cheapest integration; Modbus available as an option
Pain Points Behind the Search
  • A float switch arrangement gave only start/stop of the make-up pump, so the tank cycled between two levels and the pumps saw varying suction head.
  • A pressure-type sensor installed at the tank bottom clogged with algae and scale and had to be lifted out for cleaning, which required a shutdown permit.
  • The summer foam caused a radar on trial to lose echo and drive the make-up valve fully open, overfilling the tank.
  • Nobody could explain to management why make-up water consumption varied from month to month, because there was no level trend.
Selection Logic

The control loop needs a stable, repeatable level signal with no moving parts and no shutdown for cleaning. The selected instrument is an 80 GHz radar level transmitter with a PTFE lens, 4–20 mA plus Modbus output, mounted on an existing handrail bracket and aimed away from the return water inlet.

Selection item Specified value Reason
Principle 80 GHz FMCW radar Narrow beam avoids the tank wall and the return inlet structure
Range / accuracy 0–10 m / ±3 mm Repeatability well inside a 1 m control band
Antenna PTFE lens, self-cleaning Reduces condensation and algae adhesion; wipe with water, no acid
Output 4–20 mA + Modbus RTU 4–20 mA for the existing DCS card, Modbus for the plant network
Damping Adjustable 1–20 s Filters surface ripple so the make-up valve stops hunting
Protection IP67 Humid tank area, washdown nearby
Installation Logic
  1. The bracket is positioned on the handrail on the side opposite the return inlet, at least 1 m from the wall, so the beam sees calm water.
  2. The antenna is set 400 mm above the maximum level, and the dead zone is confirmed against the tank drawing before drilling.
  3. Damping is set to 10 s and the output is linearised in the DCS; controller output is then tuned to the 1 m band.
  4. The echo map is taught under two conditions — calm water and full return flow — so the inlet structure is masked in both cases.
  5. Foam handling is configured in the device: a moderate filter with a hold time of 10 s, plus a DCS sanity check that rejects a jump of more than 0.3 m in 30 s.
  6. Because the transmitter is non-contact, the tank is never opened and no shutdown permit is needed for maintenance.
Results
  • Continuous level replaced two-point pump control, so the make-up valve now modulates and the suction head stays stable.
  • Signal damping and the jump-reject logic removed the overfill event caused by foam.
  • Cleaning is now a wipe of the lens from the walkway, with no shutdown and no lifting of a heavy probe out of the tank.
  • Level trend data is available for the monthly water balance, so make-up consumption differences can finally be explained.
What Buyers Usually Ask Before Ordering

Will the radar handle the foam? Light foam is tolerable with a filter and hold time. Thick stable foam needs a guided-wave radar with a stilling tube.

Can I keep my existing DCS card? Yes — order the 4–20 mA version and use the Modbus port for diagnostics or a second system.

Procurement Decision Checklist
  • Provide the tank drawing and the position of the return inlet, not only the tank dimensions.
  • Ask for adjustable damping and a jump-reject function in the DCS specification.
  • Specify a PTFE lens where algae or scale is expected, and confirm it can be cleaned without removing the housing.
  • Keep one spare antenna seal in stock; it is the lowest-cost part with the highest failure impact.