Check Valve Case Study: Backflow Prevention at a Municipal Sewage Lift Station with Dual Pumps

2026/11/25
Latest company blog about Check Valve Case Study: Backflow Prevention at a Municipal Sewage Lift Station with Dual Pumps

Background and Operating Conditions

A municipal sewage lift station runs two pumps that alternate duty to push wastewater to a treatment plant. Each pump discharge needs a check valve so that when one pump stops, the other does not push flow backward through it, and so the line does not drain back into the wet well. The fluid carries solids and rags, and the station operates automatically with frequent starts. Maintenance crews search for a sewage check valve that passes solids without clogging and closes cleanly on every pump stop.

The Challenge

The existing check valves were the wrong type for raw sewage: narrow passages caught rags, and the discs no longer seated, so flow leaked backward and one pump short-cycled against the other. Every stop sent a reverse-flow surge that produced water hammer, stressing the pipework and the pumps. Callouts to clear jammed or leaking valves had become routine, and pump wear was increasing.

Engineering Selection

Full-port swing check valves with a resilient seat were selected so solids pass through the wide opening instead of catching, and the disc closes quickly on flow reversal to limit water hammer. Spring assistance helps closure stay controlled through frequent cycling.

CriterionSelection
Solids handlingFull-port swing, wide flow area
SealingResilient seat for reliable reseating
ClosureSpring-assisted to limit water hammer
MaintenanceAccessible cover for clearing debris

Installation and Commissioning Logic

The check valves were installed on the horizontal discharge headers with the flow arrow aligned to pump discharge, positioned so maintenance can open the cover to clear any debris without removing the valve. The dual-pump alternation was tested by running each pump in turn and confirming that the idle pump does not backflow and that closure does not produce a noticeable surge, before the station returned to automatic operation.

Results

Backflow through the idle pump stopped, so the running pump no longer short-cycles and the line holds its pressure between starts. The full-port design passes solids instead of clogging, cutting emergency callouts, and the controlled, spring-assisted closure reduces the water hammer that had been stressing pipes and pumps.

Procurement Decision

The utility now specifies full-port, resilient-seated check valves for raw-sewage duty and keeps a spare on the shelf for each station. The decision weighed clog resistance and maintainability over the lowest bid, because a check valve that jams or leaks costs far more in callouts and pump wear than the price difference on the valve itself.