Metal Tube Flowmeter Two Reed Switch Alarm Points 4-20mA IP65 Pump Protection
Product Details
| Model: | QWYB-LZD512 | Water Flow Range: | 10-2500 L/h (DN15-DN50) |
|---|---|---|---|
| Gas Flow Range: | 0.5-60 M3/h | Accuracy: | 1.5 Liquid / 2.5 Gas |
| Alarm Points: | 1-2 SPDT Reed Switches, Independently Adjustable On The Scale | Switch Rating: | 30 V DC, 0.2 A Maximum, Dry Contact |
| Alarm Repeatability: | Within 1% Of Full Scale | Output Signal: | 4-20 MA Two Wire, RS485 Optional |
| Wetted Material: | 304 Or 316L Stainless Steel | Working Pressure: | 1.6 / 2.5 / 4.0 MPa Options |
| Medium Temperature: | -20 To 120 C | Protection Class: | IP65, Exd II BT4 Enclosure Option |
| Highlight |
Two Point Reed Switch Alarm,Pump Dry Run Flow Switch,IP65 Stainless Steel Housing |
||
Product Description
Metal Tube Flowmeter That Switches a Pump Off Before the Seal Runs Dry
two adjustable reed switch points | 4-20 mA output | IP65 | DN15-DN50
A flow reading that nobody watches is only a record of what already went wrong. This page is about the version of the metal tube flowmeter that acts on the reading: two magnetically coupled switches, set anywhere on the scale, wired into a pump starter, a dosing pump or a PLC input. It covers why that matters, how the switching actually happens, what the housing protects, and how to set points that a control room can trust.
Why the Expensive Failures Are the Ones Nobody Noticed at the Time
Mechanical seals, mechanical seals and pump bearings fail in the same way: they run dry for a few minutes and then run hot. A cooling water branch that loses flow because a strainer blinded overnight gives no alarm on most installations, because the pump motor current barely changes and the discharge pressure stays close to normal. The cost appears later as a seized pump, a warped seal face, or a batch that was dosed without carrier water.
The same pattern appears on dosing skids. A metering pump keeps stroking against a closed valve or an empty tank, and the control system has no way to know that nothing is being added. Both situations are cheap to prevent if the flow instrument can open or close a contact at a chosen flow value, which is exactly what a reed switch alarm point does.
How a Magnetic Float Trips a Switch Without Touching the Medium
A small permanent magnet is embedded in the float assembly. As the float rises and falls inside the tapered stainless tube, the field moves past the wall of the tube, and a reed switch mounted on the outside of the scale frame closes when the field is strong enough. Nothing penetrates the pressure boundary, so there is no gland, no dynamic seal and no wet wiring to fail.
The set point is simply the mechanical position of the switch bracket. Loosen the bracket, slide it to the engraved value you want, tighten it, and the switching point has moved. Two brackets give a low alarm and a high alarm on the same meter, which is why one instrument can both protect a pump and confirm that a batch is running at the intended rate.
- Switching repeatability is within 1% of full scale, dominated by the bracket position you set rather than by the float.
- The magnet assembly is balanced, so adding the switch does not change the flow indication on the scale.
- Dry contacts mean you choose the logic: normally open for alarm-on-low-flow, normally closed for fail-safe wiring.
One Meter, Three Signals: Local Pointer, Current Loop, Dry Contacts
Control rooms rarely need the same thing from every meter. A field operator wants a pointer he can read from the walkway; the PLC wants a 4-20 mA value for trending; the safety interlock wants a hard contact that does not depend on firmware. This body provides all three from one pipe connection, and the three do not compete: the pointer is mechanical, the current loop is independent, and the contacts are galvanically separate dry circuits.
- IP65 stainless housing - washdown on a skid and rain on an outdoor pipe rack are both acceptable.
- Exd II BT4 option - the same measuring body in a flameproof enclosure for solvent and fuel gas areas.
- LCD option with totaliser - instantaneous flow plus an accumulated volume for batch reconciliation.
- Front-adjustable brackets - set points changed on site in minutes, no recalibration of the meter needed.
- Threaded or flanged ends - DN15 to DN50 in the same product family, so spares are common across a plant.
- Pressure classes to 4.0 MPa - covers most cooling water and compressed air headers without a special build.
Setting Alarm Points the Control Room Can Actually Use
Three details decide whether an interlock helps or becomes a nuisance. First, put the low set point at roughly 60% of normal flow, not at 10%, because a partially blinded strainer still passes flow and you want to catch it early. Second, expect a small band between make and break, so never set the alarm point inside the normal operating fluctuation of a pulsating pump. Third, add a 3-5 second delay in the PLC logic to ride through start-up transients, and wire the contact in the fail-safe direction so a broken cable reads as an alarm rather than a healthy line.
If your control cabinet supplies 24 V DC with a few milliamps of input current, the standard contact rating of 30 V DC and 0.2 A is comfortable. For AC contactors or long cable runs, use a relay in between: a reed switch is not a power switching device, and arcing is the quickest way to lose one.
Two Operating Conditions Compared
| Condition | A. Typical failure mode without the meter | B. Same line after the meter is installed |
|---|---|---|
| What happens after a strainer blinds | Pump keeps running, seal runs dry, failure appears as a leak or a seized shaft days later. | Flow falls below the low set point, contact opens, pump stops within the PLC delay and the alarm is logged. |
| Dosing without carrier water | Metering pump strokes into a dry line, chemical concentrates in the injection quill and crystallises. | Interlock holds the dosing pump until main line flow is proven, so dosing only happens with flow. |
| Who notices the fault | Whoever finds the damage on the next shift. | The control room, at the moment the flow drops, with the value that caused it. |
| Spare parts consumed | Seals, bearings and occasionally a complete pump and motor. | One strainer basket cleaning and a switch that costs less than a seal kit. |
Two Field Installations
Case 1 - Cooling water header, polymer extrusion plant (Thailand)
| Industry | Polymer compounding and extrusion |
| Site / region | Rayong, Thailand |
| Medium | Cooling tower water, 1.5-2 mm suspended solids |
| Flow range | 0.9-2.4 m3/h per extruder branch, low alarm at 1.2 m3/h |
| Pressure and temperature | 0.45 MPa, 30-42 C |
| Connection | DN25 flanged, ANSI 150 |
| Configuration supplied | QWYB-LZD512, 316L body, one SPDT low alarm, 4-20 mA to PLC, IP65 head |
| Previous problem | Two shaft seals and one pump failed in eighteen months, both after weekend strainer blinding |
| What changed | Low flow contact wired to the pump starter through a 4 second PLC delay, alarm also shown on the line HMI |
| Measured result | Three strainer blockages caught before seal damage in the first year, zero seal failures since |
Case 2 - Polymer dosing interlock, wastewater plant (South Africa)
| Industry | Industrial effluent treatment |
| Site / region | Gauteng, South Africa |
| Medium | Polymer solution, 0.5% concentration, mildly viscous |
| Flow range | 35-85 L/h carrier water, dosing enabled above 40 L/h |
| Pressure and temperature | 0.3 MPa, 18-30 C |
| Connection | 1/2 inch BSP threaded |
| Configuration supplied | QWYB-LZD512, 304 body, two SPDT points, one for enable and one for high flow alarm, LCD totaliser |
| Previous problem | Polymer was dosed during backwash and during pump stoppages, wasting chemical and blinding the membrane skid |
| What changed | Enable contact wired in series with the dosing pump run permit, high point alarm at 90 L/h sent to the SCADA alarm list |
| Measured result | Polymer usage down 22%, membrane cleaning interval extended from 3 weeks to 7 weeks |
Six Reasons This Configuration Sells Into Retrofits
- No wiring at the wetted side - the switch sits outside the pressure boundary, so there is no seal to leak on a 4.0 MPa header.
- Set points adjustable on site - commissioning changes do not require a new meter or a factory return.
- Three outputs from one tapping - pointer, 4-20 mA and dry contacts avoid three separate instruments in the line.
- Interlock without firmware - a hard contact still works when the controller is being updated.
- Common body across DN15-DN50 - one spare float and bracket set covers the whole line size range.
- Tested before dispatch - every alarm point is verified against a calibrated flow reference and recorded on the test sheet.
Technical Specifications
| Model | QWYB-LZD512 |
| Water flow range | 10-2500 L/h, DN15 to DN50 |
| Gas flow range | 0.5-60 m3/h |
| Accuracy | 1.5 liquid / 2.5 gas |
| Alarm output | 1-2 SPDT reed switches, independently adjustable |
| Switch rating | 30 V DC, 0.2 A maximum, dry contact |
| Alarm repeatability | within 1% of full scale |
| Signal output | 4-20 mA two wire; RS485 or HART optional |
| Wetted material and pressure | 304 or 316L stainless steel, 1.6 / 2.5 / 4.0 MPa |
| Temperature and protection | -20 to 120 C, IP65 standard, Exd II BT4 option |
| Connection | Threaded or flanged, DN15-DN50, DIN or ANSI |
FAQ
Will the reed switch work directly with a 24 V PLC input?
In most cases yes, provided the input draws a small current and the cable run is short. The standard contact is rated 30 V DC at 0.2 A maximum, and a typical PLC digital input presents 5-10 mA at 24 V, well inside that window. Two cautions: keep total cable length under about 50 m to limit capacitance, and avoid routing the switch cable in the same tray as motor or VFD cables, because a reed contact is a low energy device and induced voltage can cause spurious pulsing. If your input is capacitive or you need long runs, interface with a 24 V relay and let the relay carry the cable. Tell us the input specification and we will confirm the wiring diagram on the quotation.
How tight is the switch point, and can it be adjusted after installation?
Repeatability is within 1% of full scale, so on a 0-2500 L/h meter the switch will break within roughly 25 L/h of the same value every time. Absolute position accuracy depends on where the bracket is clamped, which is why the scale frame carries a fine index mark and the bracket is set with a screwdriver on site. Adjustment is allowed while the line is running: slide the bracket until the contact changes state at the flow you want, then lock it. There is a natural dead band between make and break of a few percent of full scale; that hysteresis is deliberate and prevents chatter when the float vibrates.
Can a second alarm point be added to a meter we already own?
If the meter is our QWYB-LZD series with a standard scale frame, a second bracket and switch assembly can be fitted in the field, but the float must already carry the magnet, which is not the case on the plain indication-only version. In practice that means a retrofit kit is only viable when the original order included at least one switch, or when the meter is returned to us. For plants that expect to add interlocks later, order the two-point version from the start: the price difference is small compared with a second instrument and a second pipe tapping. Send us the serial number and we will confirm what your existing body can accept.
What happens on power failure or if the float sticks?
The contacts are passive, so a power failure leaves them in their last mechanical state, which is why wiring matters more than the switch itself. Wire the low flow contact in the fail-safe direction, normally closed for healthy flow, so a broken cable, a loose terminal or a power loss to the interlock circuit all read as an alarm rather than as a healthy line. A sticking float is the harder case: dirt on the tube wall can hold the float above zero, which reads as false flow. Add a low-flow check against pump run status in the PLC, and clean the tube at the same interval as the strainer basket.
Related Meters From the Same Line
These pages cover the neighbouring duties, from signal-only versions to non-intrusive options:
- Metal tube float flowmeter with 4-20 mA and HART output - indication and signal, no alarm contacts.
- IP65 and IP67 safety metal tube flowmeter - higher ingress protection for outdoor and washdown areas.
- High pressure metal tube float flowmeter - up to 4.0 MPa and above for test benches.
- Clamp-on Doppler ultrasonic flowmeter - for slurry and sludge where an inline float would block.
Tell us the normal flow, the flow value at which the pump must stop, your control voltage and the pipe standard. We will return a wiring diagram and a quotation with the set points already configured.
Product Highlights
Metal tube float flowmeter with one or two adjustable reed switch alarm points, 4-20 mA output and IP65 stainless steel housing. Dry contacts drive pump protection and dosing interlocks. Inquire with your alarm set points and coil voltage.
Petroleum Radar Level Gauge 26GHz High Temperature Industrial
Petroleum Radar Level Gauge brings 26GHz radar precision and high-temperature capability to oil storage tank measurement. Every millimeter of level is tracked accurately to prevent inventory loss and safety risk. Inquire now for specifications.
Portable FMCW Radar Level Gauge IP67 Liquid Measurement Sensor
Portable FMCW Radar Level Gauge brings laboratory-grade radar measurement to any tank in the plant or field. With IP67 protection and quick setup, it delivers accurate liquid level readings without permanent installation. Contact us for specifications.
Intelligent Digital Pressure Transmitter Multi-Unit LCD Alarm Relay
Digital pressure transmitter with integrated backlit LCD, local pushbutton configuration, and alarm relay output. Multi-unit display (MPa, kPa, bar, psi, kgf/cm²), IP67 protection, and HART 7 protocol for smart plant integration.
Universal Gauge Pressure Transmitter 4-20mA Oil Water Gas Measurement
Universal Gauge Pressure Transmitter measures pressure relative to the atmosphere for pump discharge, line pressure, tank head and filter differential applications. With 4-20mA output, it suits oil, water and gas measurement. Contact us for range options.
Please use our online inquiry contact form below if you have any questions, our team will get back to you as soon as possible.