Geothermal Well Water Level Monitoring: Wireless Level Transmitter Case with 4G and Solar Power

2026/10/27

Dernières nouvelles de l'entreprise Geothermal Well Water Level Monitoring: Wireless Level Transmitter Case with 4G and Solar Power
Site Conditions: What a Geothermal Well Actually Looks Like

This case describes a production geothermal well used for district heating. The wellhead water temperature runs 60–95 °C, the static water level sits 20–80 m below the wellhead, the submersible pump is set at 80–200 m, and there is no reliable low-voltage power at the wellhead — the nearest usable supply is several hundred metres away across an access road. The water carries dissolved gas, fine sand and a strong carbonate scaling tendency. Winter ambient drops to −15 °C, and the wellhead pit floods after rain.

Field parameter Typical value on site Why it changes the instrument choice
Wellhead water temperature 60–95 °C Standard PVC or PE cables soften; the sensor cable and diaphragm must be rated for continuous hot water
Static level below wellhead 20–80 m Measurement span is large, so accuracy must be specified as a percentage of span, not of full scale
Wellhead power supply None (off-grid) Loop-powered 4–20 mA cannot drive a remote link; a battery/solar wireless node is required
Water quality Dissolved gas, sand, scale Diaphragm fouling and gas pockets cause drift on pressure-type sensors
Ambient conditions −15 °C in winter, flooded pit Enclosure and antenna must be IP67 or better with frost protection
Why the Previous Setup Was Unreliable
  • Manual dip measurement once a week could not detect a falling water level caused by pump drawdown, so the pump occasionally ran dry and tripped on overload.
  • A standard submersible transmitter with a PVC cable hardened and cracked at the wellhead gland within one heating season.
  • No data path to the control room: the heating station only learned about a well problem when a resident called about cold radiators.
Selection Logic

The requirement was a continuous reading of dynamic water level in a hot, scaling, off-grid well, delivered to a heating control room 1.2 km away. The chosen configuration was a high-temperature submersible level transmitter with a vented, heat-resistant cable, mounted inside a 1.5-inch sounding pipe strapped to the pump riser, connected to a battery-powered remote terminal unit with a 4G module and a 40 W solar panel.

Selection item Specified value Reason
Sensor type Submersible pressure transmitter, vented gauge Radar from the wellhead was rejected: steam, foam and a narrow casing create false echoes at this depth
Wetted material 316L diaphragm with PTFE facing Limits carbonate scale adhesion and allows acid cleaning without damaging the diaphragm
Temperature rating Continuous 90 °C, cable 105 °C Matches measured wellhead temperature with margin
Measuring range 0–150 m H₂O Covers pump setting depth plus drawdown
Accuracy ±0.5 % of span Gives roughly ±0.75 m at full span, adequate for pump protection
Output and link RS485 Modbus to RTU; 4G to server; local 4–20 mA Local loop for the station PLC, wireless for the remote control room
Power 3.6 V lithium pack plus 40 W solar, 12 V buffer Keeps the node alive through 10 cloudy winter days
Protection IP68 sensor, IP67 enclosure Flooded pit and hose-down conditions
Installation Logic
  1. The sounding pipe is fixed to the pump riser at 3 m intervals, with the open bottom 2 m above the pump intake so sand and gas stay out of the sensing zone.
  2. The vent tube is routed upward with a desiccant cartridge and a drip loop; a blocked vent is the most common cause of reading error on vented sensors.
  3. The cable gland is sealed with a high-temperature gasket rated above 100 °C, and a 30 cm service loop is left outside the wellhead for future re-termination.
  4. The solar panel faces south at 45° with a lightning arrester on the DC side and a separate earth electrode at the wellhead.
  5. Alarm thresholds are set at the control room: low-low level stops the pump, low level raises a warning, and a rate-of-fall alarm flags a sudden drop.
Results After Commissioning
  • Water level is refreshed every 60 seconds and displayed on the heating station screen and on a mobile page, replacing the weekly manual dip.
  • Dry-run trips stopped, because the low-low threshold now acts on a live level signal instead of a delayed current-based protection.
What Buyers Usually Ask Before Ordering

Can I use a radar gauge instead? For an open wellhead with a wide casing, yes; for a narrow casing with steam and foam, a submersible pressure sensor is more stable.

Procurement Decision Checklist
  • Confirm continuous temperature at the wellhead, not the average, and require a cable rating above it.
  • Confirm the sounding pipe diameter and the distance from the wellhead to the lowest dynamic level.
  • Ask for the Modbus register map and alarm logic in writing before shipment.
  • Order one spare transmitter and one spare cable gland — the cable gland is the part that fails first.